Categories
Article No. 296.902.374
E-Number 808 453 010
Technical specification
SPD type T1 / T2 / T3  
Number of poles 3  
max. discharge current (Imax) 70  
Nominal line voltage Un AC 230  
Continuous voltage AC max. 255  
Nominal frequency [fn] 0.0 - 100.0 Hz
Impulse current [Iimp]_(10/350) 25  
Discharge current max. (8/20) µs [Imax] 70  
Nominal discharge surge current (8/20) 30  
Combined shock [Uoc] 20  
Voltage protection level [Up] 1.5  
Protection level max. (at 5kA) 0.65  
Protection level max. (at 12.5kA) 0.8  
Protection level max. (at Imax) 1.5  
Operating current [Ic] 0  
Follow current [IF] 0  
follow current extinguishing capability [Ifi] Unendlich kA eff  
Response time [ta] ≤20 ns  
TOV-voltage L-N [UT] 450 V / 5 sec.  
TOV-voltage N-PE [UT] 1200 V / 200 ms / 300 A  
TOV-voltage L-PE [UT] 1454 V / 200 ms / 300 A  
Short circuit resistance (Icw) 25  
Fault indication mechanisch, Rot  
Temperature range -40.0 - 85.0 °C
Degree of protection IP20  
Fuse max. (gG) 315  
Mounting on Hutschiene 35 mm  
Material housing  
Signaling on the device Optic  
Signaling contact Yes  
Connection cross section solid / stranded max. 1.5  
Switching capacity signaling contact 250 V/0,5 A (AC) / 125 V/0,25 A (DC)  
System configuration  
Energetically coordinated protective effect to the terminal Yes  
Construction size 6 modular spacing  
Exhausting No  
Yes  
Nominal cross section conductor 6.0 - 50.0 mm²
Voltage protection level L-N [Up] 1.5  
Mounting method DIN rail (top hat rail) 35 mm  
Degree of protection (IP) IP20  
Standards
Homologation UL  
Test standards Germany  
Test standards Europe EN 61643-11  
Test standards International IEC 61643-11  
Test standards USA UL 1449 d.3  
Commercial specification
Customs number 85363000  
country of origin CE*  
Logistic specification
VPE Weight 0.896