Article No. 290.440.021
E-Number 808 490 230
Technical specification
SPD type T1 / T2  
Impulse current [Iimp]_(10/350) 12.5 kA  
max. discharge current (Imax) 50 kA  
Response time [ta] 20 ns  
Voltage protection level [Up] 1.3 kV  
Nominal cross section conductor (min/max) 2.5 - 25.0 mm²
Signaling contact Yes  
Nominal discharge surge current (8/20) 20 kA  
Nominal frequency [fn] 50.0 - 60.0 Hz
Nominal line voltage Un AC 230 V  
Continuous voltage AC max. 255 V  
Discharge current max. (8/20) µs [Imax] 50 kA  
Follow current [IF] 0 kA  
follow current extinguishing capability [Ifi] unendlich kA eff  
TOV-voltage L-N [UT] 440 Vac  
Short circuit resistance (Icw) 25 kA  
Fault indication Mechanisch, Rot  
Temperature range -40.0 - 85.0 °C
Degree of protection IP 20  
Fuse max. (gG) 160 A  
Mounting on Hutschiene 35 mm  
Material housing  
Signaling on the device Optic  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
Material housing  
Mounting method  
Remote signalling Yes  
Degree of protection (IP) IP65  
Voltage protection level L-N [Up] 1.3 kV  
Total discharge current (8/20) (L N-PE) 50 kA  
Standards
Test standards Germany  
Test standards International IEC 61643-11  
Test standards USA UL 1449 ed.3  
Test standards Europe EN 61643-11  
Homologation VDE, ÖVE und UL  
Commercial specification
Customs number 85389000  
country of origin CE*  
Logistic specification
VPE Weight 0.496 kg  
Replacement module

Replacement module 296.045.570