Categories

Junction box PV GAK 212 PG

Characteristics
Generator boxes with preassembled surge protection and grounding plate:

Legend
a) type 1+2 GAK + DIS 60 VGPVS-1000-4ST-2MPP
b) type 1+2 GAK + DIS 50 PVS-1000-4ST-2MPP
c) type 1+2 GAK + DIS 50 VGPVS-1000-4ST-2MPP
d) type 2 GAK + DIS 50 PV-1000-4ST-2MPP

SPD type
T1 / T2  
Operation voltage max. [Uc]
≤1200VDC  
Number of poles
2  
Nominal line voltage Un DC
1000 V  
Protection level max. (at 5kA)
2.1 kV  
Protection level max. (at 12.5kA)
2.3 kV  
Operating current [Ic]
0 kA  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
Unendlich kA eff  
Fault indication
mechanisch, Rot  
Temperature range
-40.0 - 85.0
Fault indication
Mechanisch, Rot  
Temperature range
-40.0 - 85.0
Material housing
 
Signaling on the device
optisch  
Material housing
 
Degree of protection
IP20  
Signaling on the device
optisch  
Connection cross section solid / stranded max.
1.5 mm²  
Material housing
 
Connection cross section solid / stranded max.
1.5 mm²  
Energetically coordinated protective effect to the terminal
Yes  
Signaling on the device
optisch  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
Connection cross section solid / stranded max.
1.5 mm²  
System configuration DC
Yes  
Energetically coordinated protective effect to the terminal
Yes  
Integrated backup fuse
No  
System configuration DC
Yes  
Exhausting
No  
Integrated backup fuse
No  
Exhausting
No  
Mounting method
DIN rail (top hat rail) 35 mm  
Total discharge current (8/20) (L N-PE)
60 kA  
Integrated backup fuse
No  
Mounting method
DIN rail (top hat rail) 35 mm  
Exhausting
No  
Degree of protection (IP)
IP20  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
degree of protection
IP65  
number of modules
20  
contract rail
DIN-Schiene  
String / MPP
4ST-2MPP  
inputs PG / MC4
PG  
outputs PG / MC4
PG  
Ground base plate
Yes  
Switching capacity voltage max. Uoc Max.
1000 V  
Switching current max. Isc. Max.
30 A  
Cross-sectional area
6 mm²  
Test standards USA
UL 1449 ed.3  
Homologation
VDE, ÖVE und UL  
Test standards Germany
 
Test standards France
UTE C61-740-51  
Test standards Germany
 
Test standards USA
UL 1449 ed.3  
Test standards France
UTE C61-740-51  
   
Article No. E-Number SPD type Operation voltage max. [Uc] Impulse current [Iimp]_(10/350) max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal cross section conductor (min/max) Signaling contact Nominal discharge surge current (8/20) Number of poles comment VPE Quantity
   
Junction box PVGAK+DIS60VG-1000-4ST-2MPP PG 296.049.357 969 111 684 T1 / T2 ≤1200VDC 12.5 40 ≤25 2.8 6.0 - 35.0 Yes 20 2 a) 1
Coarse and middle protection PV GAK+DIS50 PVS-1000-4ST-2MPP 296.049.957 969 111 714 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.6 2.5 - 25.0 Yes 15 2 b) 1
Junction box PV GAK+DIS50VG-1000-4ST-2MPP 296.049.557 969 111 694 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.8 2.5 - 25.0 Yes 2 c) 1
Junction box PVGAK+DIS50-1000-4ST-2MPP PG 296.049.757 969 111 704 T2 ≤1200VDC 5 40 ≤25 2.6 2.5 - 25.0 Yes 15 2 d) 1